Massachusetts College Enhances AHU Performance with MeeFog Humidification and Evaporative Cooling

MeeFog provided a tailored solution with humidification for air handling units (AHUs) 1-4 & 6, and evaporative cooling for heat recovery units (HRUs) 1-4.  The system consists of one pump rack with dual 5 GPM pump units, 5 hp motors, variable frequency drives (VFD), and pressure transducers. These components are mounted on one stainless steel pump rack with a single-point power connection, managed by a PLC that monitors both pump units and provides automatic switchover for seamless operation.

 

Project Conditions:

Location: Amherst, Massachusetts
Entering air conditions: 66°F db / 44°F wb
Leaving air conditions: 55°F db / 42°F wb
MeeFog Scope: Equipment supply & start-up supervision
Maximum fog system power: 2 x 5 HP

Humidification:

MeeFog™ nozzle count: 121
Humidification capacity: 1,530 lbs/hr

Evaporative Cooling:

MeeFog™ nozzle count: 140
Cooling capacity: 20°F reduction

 

Humidification Equipment Schedule

Learn More

Want to learn more about how MeeFog systems can enhance your facility’s energy efficiency?

Other Related Blog Articles

Grand Valley State University (GVSU) – Energy-Efficient Humidification with MeeFog

Project Profile: GVSU uses MeeFog to humidify one air handling unit and six greenhouse zones  ...

Evaporative Cooling for Arizona State University’s LEED Platinum Certified Research Lab

Project Profile: Explore the MeeFog energy recovery system that delivers 15°F cooling while enhancing sustainabilit...
university with modern architecture and scenic setting along the Grand River

Efficient Humidification Solutions for Sustainable Campus Development

Case Study: Grand Valley State University strategically implemented a cost-effective MeeFog centralized humidificati...