U.S. Embassy Cools Diesel Generators with MeeFog
Gas Turbine Inlet Air Cooling![](https://www.meefog.com/wp-content/uploads/KABUL-US-Embassy-1.jpg)
The U.S. Embassy in Kabul, Afghanistan needed to cool two large rooms that house the diesel generators that power the embassy. They installed eight MeeFog systems to provide 36°F of evaporative cooling for each of the eight air inlet serving the 2-MW diesel generator. Each inlet has a fog system consisting of a 1000-psi fog pump unit, staging valves, interconnecting feedlines and a fog nozzle array.
Project Conditions:
Location: Kabul, Afghanistan
Hot day conditions: 93.5 °F and 11% RH
Model: Diesel Generators
Elevation: 6,000 feet
Mee’s scope of work: Equipment supply
Max cooling per Generator: 36°F
Fog System Design:
Cooling Stages: 8
Operating Pressure: 1,000 psig
Fog Droplet Size: 10 microns (D32)
MeeFog™ Nozzle Count: 780
Nozzle Flow Rate: 0.013 gpm
Max. Skid Water Flow: 6.9 gpm
Max. Power Requirement: 10 HP
Learn More